PRODUCT DESCRIPTION AND SPECIFICATIONS

Table 1 - Heating Capacities, BTU per hr per lin. ft. 65 degrees entering air temperature I-B-R approved
| model |
Nom. Tube Size |
Fin Dimensions H X W |
Thick- ness |
Fin Spacing Fins/Ft. |
Water Rate GPM |
Hot Water Ratings Average Water Temperature degrees F |
Heat Base 750-1B |
3/4" CPR. |
2 1/8" X 2 1/2" Natural Finish |
.008 |
54.5 |
|
| 150 |
160 |
170 |
180 |
190 |
200 |
210 |
220 |
230 |
240 |
| 410 |
480 |
550 |
610 |
690 |
760 |
829 |
900 |
970 |
1040 |
| 390 |
450 |
520 |
580 |
650 |
720 |
780 |
850 |
920 |
980 |
|
All the above I-B-R Ratings are based on active length, which is 3" less than total length, and includes a 15% addition for heating effect.
Ratings: Heating capacities are listed in Table 1 for two flow rates: 1 GPM and 4 GPM. The use of I-B-R Ratings at 4 GPM is limited to installations where the water flow rate through the baseboard unit is equal to or greater than 4 GPM. Where the water flow rate through the baseboard is not known, the I-B-R Ratings at the standard flow of 1 GPM must be used.
Table 2 - Factors for ratings at flow other than standard and pressure drop values
| Rate of Flow GPM |
1.0 |
1.5 |
2.0 |
2.5 |
3.0 |
3.5 |
4.0 |
4.5 |
5.0 |
6.0 |
| Factor |
1.000 |
1.016 |
1.028 |
1.038 |
1.045 |
1.051 |
1.057 |
1.062 |
1.067 |
1.074 |
Pressure Drop 3/4" Tube Mill inches per ft. |
47 |
96 |
157 |
230 |
320 |
420 |
525 |
650 |
775 |
1060 |
Note: If the calculated water flow rate through a baseboard unit in a completely designed hot water heating system is greater than the standard flow rate (1 GPM), the rating of that unit may be increased by multiplying the standard I-B-R Rating at 1 GPM by the factor shown for the calculated flow rate.