1. Disconnect power to water heater.
2. Close hot and cold isolation and service valves and remove service caps.
3. Pour 1.5 gallons of water into bucket and place under water heater.
4. Add contents of 1 quart bottle of Whitlam Flow-Aide into bucket (Bucket should be filled approximately 1/2 full).
5. Connect one hose to pump, and other end of same hose to cold service valve. Place pump in bucket.
6. Connect second hose to hot service valve. Place other end in bucket.
7. Open both hot and cold service valves.
8. Plug pump into grounded receptacle.
9. Allow pump to circulate Whitlam Flow-Aide solution through heater for 30-45 minutes. Unplug pump.
10. Close cold service valve. Remove hose from cold service valve, and replace service cap.
11. Disconnect the hose from the pump and remove pump from bucket. Discard Whitlam Flow-Aide solution.
12. Flush tankless water heater for 3-5 minutes or until water flows clear by opening the cold isolation valve and allowing water to exit through the hot service valve into a drain or bucket. If using a bucket, empty periodically.
13. Close hot service valve. Remove hose from service valve and replace service cap.
14. Open hot isolation valve.
15. Connect power to water heater and return appliance to service.